SECTION 15190
MECHANICAL IDENTIFICATION
PART 1 - GENERAL
1.01 SECTION INCLUDES
A. Nameplates.
B. Stencils.
C. Pipe Markers.
1.02 RELATED SECTIONS
A. Section 09900 - Painting: Identification painting.
1.03 REFERENCES
A. Not Used.
1.04 SUBMITTALS
A. Submit under provisions of Section 01300.
B. Submit list of wording, symbols, letter size, and color coding for mechanical identification.
C. Product Data: Provide manufacturers catalog literature for each product required.
D. Samples: Submit two labels and tags, 1-1/2 x 1-1/2 inch in size.
E. Manufacturer's Installation Instructions: Indicate special procedures, and installation.
1.05 PROJECT RECORD DOCUMENTS
A. Submit under provisions of Section 01700
PART 2 - PRODUCTS
2.01 NAMEPLATES
A. Manufacturers:
1. Seton Name Plate Corporation.
2. Other acceptable manufacturers offering equivalent products.
a. Badger Tag & Label Co..
b. W.H. Brady Co..
c. Bunting Stamp Co., Inc.
B. Description: Laminated three-layer plastic with engraved black letters on white contrasting background color. Provide name plates with two mounting holes and screws, pressure sensitive tape backing.
C. Description: Minimum 0.020 inch thick aluminum plate with natural aluminum border black enamel background and natural aluminum lettering. Provide name plates with pressure sensitive tape backing.
2.02 STENCILS
A. Manufacturers:
1. Seton Name Plate Corporation.
2. Other acceptable manufacturers offering equivalent products.
a. Badger Tag & Label Co.
b. Bunting Stamp Co., Inc.
c. W.H. Brady Co.
B. Stencils: With clean cut symbols and letters of following size:
1. 3/4 to 1-1/4 inch (20-30 mm) Outside Diameter of Insulation or Pipe: 8 inch (20) mm) long color field, 1/2 inch (15 mm) high letters.
2. 1-1/2 to 2 inch (40-50 mm) Outside Diameter of Insulation or Pipe: 8 inch (200 mm) long color field, 3/4 inch (20 mm) high letters.
3. 2-1/2 to 6 inch (65-150 mm) Outside Diameter of Insulation or Pipe: 12 inch (300 mm) long color field, 1-1/4 inch (30 mm) high letters.
4. 8 to 10 inch (200-250 mm) Outside Diameter of Insulation or Pipe: 24 inch (600 mm) long color field, 2-1/2 inch (65 mm) high letters.
5. Over 10 inch (250 mm) Outside Diameter of Insulation or Pipe: 32 inch (800 mm) long color field, 3-1/2 inch (90 mm) high letters.
6. Ductwork and Equipment: 2-1/2 inch (65 mm) high letters.
C. Stencil Paint: As specified in Section 09900, semi- gloss enamel, colors conforming to ASME A13.1.
2.03 PIPE MARKERS
A. Manufacturers:
1. Seton Name Plate Corporation.
2. Other acceptable manufacturers offering equivalent products.
a. Badger Tag & Label Co.
b. Bunting Stamp Co., Inc.
c. W.H. Brady Co.
B. Color: Conform to ASME A13.1.
C. Plastic Pipe Markers: Factory fabricated, flexible, semi- rigid plastic, preformed to fit around pipe or pipe covering; minimum information indicating flow direction arrow and identification of fluid being conveyed.
D. Plastic Tape Pipe Markers: Flexible, vinyl film tape with pressure sensitive adhesive backing and printed markings.
E. Underground Plastic Pipe Markers: Bright colored continuously printed plastic ribbon tape, minimum 6 inches (150 mm) wide by 4 mil (0.10 mm) thick, manufactured for direct burial service.
PART 3 - EXECUTION
3.01 PREPARATION
A. Degrease and clean surfaces to receive adhesive for identification materials.
B. Prepare surfaces in accordance with Section 09900 for stencil painting.
3.02 INSTALLATION
A. Install plastic nameplates with adhesive. Apply with sufficient adhesive to ensure permanent adhesion and seal with clear lacquer.
B. Apply stencil painting in accordance with Section 09900.
C. Install plastic pipe markers in accordance with manufacturer's instructions.
D. Install plastic tape pipe markers complete around pipe in accordance with manufacturer's instructions.
E. Install underground plastic pipe markers 6 to 8 inches (150 to 200 mm) below finished grade, directly above buried pipe.
F. Identify pumps, chemical equipment, tanks, and treatment devices with plastic nameplates. Small devices, such as in-line pumps, may be identified with chain attached nameplates.
G. Identify control panels and major control components outside panels with plastic nameplates.
H. Identify piping with plastic pipe markers. Use tags on piping 3/4 inch (20 mm) diameter and smaller. Identify service, flow direction, and pressure. Install in clear view and align with axis of piping. Locate identification not to exceed 20 feet (6 m) on straight runs including risers and drops, adjacent to each valve and Tee, at each side of penetration of structure or enclosure, and at each obstruction.
I. Identify ductwork with aluminum nameplates. Identify with air unit identification number and area served. Locate identification at air unit, at each side of penetration of structure or enclosure, and at each obstruction.
END OF SECTION
|
This Section:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
Sections: 1 2 3 4 6 7 8 9 10 11 13 14 15 16 |
Rembco Geotechnical Contractors specializes in slope stabilization, foundation repair and support, shoring, grouting, soil nails, micropile installations, and sinkholes. We are experienced in these applications: micro piles, sinkhole repair, permeation grouting, pressure grouting, soil nails, chemical grouting, micropiles, compaction grout, rock anchors and compaction piles. Our specialties are rock anchor, chemical and compaction grouting, mini piles, sinkhole repair, micropiles, and soil nailing. We use a problem-solving approach in the geotechnical portions of buildings, bridges, water plants, sewage plants, tunnels, sinkholes, caisson, and roads. Rembco techniques apply when adding new real estate structures: especially rock anchor, microfine grouting, soil nailing, micropile installations for foundation support. Add URL Construction, Drilling and Concrete