PART 1 - GENERAL
01 SECTION INCLUDES
A. Motor control centers.
02 REFERENCES
A. ANSI/NEMA ICS 6 - Enclosures for Industrial Controls and Systems.
B. NEMA AB 1 - Molded Case Circuit Breakers.
C. NEMA ICS 2 - Industrial Control Devices, Controllers, and Assemblies.
D. NEMA PB 1.1 - Instructions for Safe Installation, Operation and Maintenance of Panelboards Rated 600 Volts or Less.
1.02 SUBMITTALS
A. Submit shop drawings and product data under provisions of applicable Sections of Division 1.
B. Indicate on shop drawings, front and side views of motor control center enclosures with overall dimensions. Include conduit entrance locations and requirements; nameplate legends; size and number of bus bars; electrical characteristics including voltage, frame size and trip ratings, withstand ratings, and time-current curves of all equipment and components.
C. Provide product data on combination motor starters, relays, pilot devices, and switching and overcurrent protective devices.
1.03 OPERATION AND MAINTENANCE DATA
A. Submit operation and maintenance data under provisions of applicable Sections of Division 1.
B. Include spare parts data listing; source and current prices of replacement parts and supplies; and recommended maintenance procedures and intervals.
1.04 DELIVERY, STORAGE, AND HANDLING
A. Deliver products to site under provisions of applicable Sections of Division 1.
B. Deliver in 48 inch maximum width shipping splits, individually wrapped for protection, and mounted on shipping skids.
C. Store and protect products under provisions of applicable Sections of Division 1.
D. Store in a clean, dry space. Maintain factory wrapping or provide an additional heavy canvas or heavy plastic cover to protect units from dirt, water, construction debris, and traffic.
E. Handle in accordance with manufacturer's written instructions. Lift only with lugs provided for the purpose. Handle carefully to avoid damage to motor control center components, enclosure, and finish.
PART 2 - PRODUCTS
03. ACCEPTABLE MANUFACTURERS - MOTOR CONTROL CENTERS
A. General Electric.
B. Square D.
C. Westinghouse.
2.02 MOTOR CONTROL CENTER
A. Motor Control Centers: NEMA ICS 2; Class I, Type B.
B. Main Overcurrent Protection: As indicated on Drawings.
C. Combination Magnetic Motor Starters: NEMA ICS2; AC General Purpose Class A magnetic controller for induction motors rated in horsepower.
1. Type: Full voltage or closed-circuit transition wye-delta reduced voltage as indicated on the Drawings.
2. Size: NEMA ICS2; size as indicated on the Drawings.
3. Coil Operating Voltage: 120 volts AC, 60 Hertz.
4. Overload Relay: NEMA ICS2; ambient compensated bimetal.
5. Auxiliary Contacts: Two field convertible contacts in addition to seal-in contact.
6. Selector Switches: NEMA ICS2; HAND/OFF/AUTO, in front cover.
7. Pushbuttons: NEMA ICS2; START/STOP, in front cover.
8. Indicating Lights: NEMA ICS2; RUN: green, STOP: red, in front cover.
9. Control Power Transformer: 120 volt secondary, VA capacity 25% greater than required for starter and all auxiliary control devices.
10. Auxiliary Control Relays - 120 volt, 10 amperes. Provide as required on control schematics indicated on the Drawings.
11. Controller Overcurrent Protection and Disconnecting Means: Motor circuit protector: NEMA AB 1; circuit breakers with integral instantaneous magnetic trip in each pole, with externally operable handle. Provide interlock to prevent opening front cover with handle in ON position. Handle lockable in OFF position.
12. Controller Overcurrent Protection and Disconnecting Means: Fusible switch assembly, NEMA KS1; quick-make, quick-break, load interrupter enclosed knife switch with externally operable handle. Provide interlock to prevent opening front cover with switch in ON position. Handle lockable in OFF position.
D. Feeder Tap Units: Molded case thermal magnetic circuit breakers, NEMA AB1; with integral thermal and instantaneous magnetic trip in each pole, with externally operable handle. Provide interlock to prevent opening front cover with handle in ON position. Handle lockable in OFF position.
E. Voltage Rating: 480 volts, three phase, four wire, 60 Hertz.
F. Horizontal Bussing: Copper, with a continuous current rating of 600 amperes minimum, match main rating if greater than 600 amperes. Include copper ground bus entire length of control center.
G. Vertical Bussing: NEMA ICS 2; copper, 300 amperes minimum, larger if required by load.
H. Integrated Equipment Short Circuit Rating: 22,000 Amps SYM.
I. Configuration: Units front mounting only, accessible from the front only.
J. Enclosure: ANSI/NEMA ICS 6; Type 1.
K. Finish: Manufacturer's standard gray enamel.
2.03 MOTOR STARTER PANELBOARD
A. Combination Magnetic Motor Starters: NEMA ICS2; AC General Purpose Class A magnetic controller for induction motors rated in horsepower.
1. Type: Full voltage or closed-circuit transition wye-delta reduced voltage as indicated on the Drawings.
2. Size: NEMA ICS2; size as indicated on the Drawings.
3. Coil Operating Voltage: 120 volts AC, 60 Hertz.
4. Overload Relay: NEMA ICS2; ambient compensated bimetal.
5. Auxiliary Contacts: Two field convertible contacts in addition to seal-in contact.
6. Selector Switches: NEMA ICS2; HAND/OFF/AUTO, in front cover.
7. Pushbuttons: NEMA ICS2; START/STOP, in front cover.
8. Indicating Lights: NEMA ICS2; RUN: green, STOP: red, in front cover.
9. Control Power Transformer: 120 volt secondary, VA capacity 25% greater than required for starter and all auxiliary control devices.
10. Auxiliary Control Relays - 120 volt, 10 amperes. Provide as required on control schematics indicated on the Drawings.
11. Controller Overcurrent Protection and Disconnecting Means: Motor circuit protector: NEMA AB 1; circuit breaker with integral instantaneous magnetic trip in each pole, with externally operable handle. Provide interlock to prevent opening front cover with handle in ON position. Handle lockable in OFF position.
B. Feeder Tap Units: Molded case thermal magnetic circuit breakers, NEMA AB1; with integral thermal and instantaneous magnetic trip in each pole, with externally operable handle. Provide interlock to prevent opening front cover with handle in ON position. Handle lockable in OFF position.
C. Enclosure: NEMA PB 1; Type 1 indoors.
D. Provide surface cabinet front with concealed trim clamps. Finish in manufacturer's standard gray enamel.
PART 3 - EXECUTION
04 INSTALLATION
A. Install motor control equipment in accordance with manufacturer's instructions. Provide working clearances as required by NEC Article 110.
B. Select and install heater elements in motor starters to match installed motor characteristics.
C. Motor Data: Provide neatly typed label inside each motor starter enclosure door identifying motor served, nameplate horsepower, full load amperes, code letter, service factor, and voltage/phase rating.
05 FIELD QUALITY CONTROL
A. Field inspection and testing shall be in accordance with applicable Sections of Division 1.
B. Inspect completed installation for physical damage, proper alignment, proper overcurrent protective device ratings and motor starter sizes, mechanical operation of disconnecting means, anchorage, and grounding.
C. Check tightness of accessible bus joints and other bolted connections using a calibrated torque wrench. Tightness shall be in accordance with manufacturers recommended values.
D. Measure insulation resistance of each bus section phase to phase and phase to ground for one minute each. Test voltage shall be 1000 volts. Minimum acceptable value for insulation resistance is 2 megohms.
E. Measure resistance between ground bus and enclosure. Maximum resistance is 0.01 ohms.
END OF SECTION
|
This Section:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
Sections: 1 2 3 4 6 7 8 9 10 11 13 14 15 16 |
Rembco Geotechnical Contractors specializes in slope stabilization, foundation repair and support, shoring, grouting, soil nails, micropile installations, and sinkholes. We are experienced in these applications: micro piles, sinkhole repair, permeation grouting, pressure grouting, soil nails, chemical grouting, micropiles, compaction grout, rock anchors and compaction piles. Our specialties are rock anchor, chemical and compaction grouting, mini piles, sinkhole repair, micropiles, and soil nailing. We use a problem-solving approach in the geotechnical portions of buildings, bridges, water plants, sewage plants, tunnels, sinkholes, caisson, and roads. Rembco techniques apply when adding new real estate structures: especially rock anchor, microfine grouting, soil nailing, micropile installations for foundation support. Add URL Construction, Drilling and Concrete